Power Cord Selection Calculator

Enter your load and environment to get the correct IEC 60320 connector family, minimum AWG gauge, NEC temperature derating, and voltage drop — instantly, in your browser.

Free tool

Size your cord

All math runs client-side using NEC Table 310.15(B)(2)(a) derating. For guidance only — consult a licensed electrician for final specification.

Your requirements

Recommendation

C13 / C14

10A at normal ambient — standard connector pair.

Minimum conductor gauge

16 AWG

Rated 13A · Derated to 10.4A at 25°C ambient

Derating breakdown

NEC temperature correction (25°C)× 1.00
Continuous load factor× 0.80
Effective capacity needed12.5A

Voltage drop (10ft run)

0.82V (0.68%)

Acceptable (below 3%)

Shop C13 / C14 cords →
Methodology: Temperature derating uses NEC Table 310.15(B)(2)(a) correction factors for 60°C-rated conductors. Continuous load factor of 0.80 applies when the load runs more than 3 hours (NEC 210.19 for branch circuits). Voltage drop is V = 2 × L × R × I where L = run length, R = conductor resistance per foot. For guidance only — consult a licensed electrician for final specification.

Need a hand?

Not sure which cord fits your rack?

Our US-based engineers will spec it with you — custom lengths, colors, and labels, with no minimum order.