By World Cord Sets Engineering Team · Updated September 2026 · 8 min read
Why locking power cords matter
Uptime Institute's outage analyses put power problems at the top of the causes of significant data-center outages, with human error behind most of them — and a cord pulled during maintenance is the most ordinary human error a rack can suffer. A locking cord turns that pull into a non-event.
A standard cord is designed to come off. IEC 60320-1's withdrawal test asks a plain C13 connector to hold each pin against a 1.5 N gauge and to release from a full three-pin gauge at no more than 50 N. The locking systems below publish 120 N (P-Lock, SSEMCO) to at least 200 N (V-Lock, Schurter) where their makers publish a figure at all; the ones that publish none are marked so below, because an unsourced number is worth less than none. In a 132 kW AI rack where one cord pull can cascade through dozens of servers, the premium for a locking cord is small against a single incident.